APF PCS is designed to correct
for harmonics and poor displacement power factor. By completing the following
information, this program will define the amount of corrective current
to be provided by APF PCS to meet the objective.
1. Review site carefully to determine
all of the loads to which APF PCS will be applied. APF PCS is best applied
to a common bus. Be sure to include all loads for proper evaluation.
2. Be sure there are no power factor capacitors downstream of the selected
CT location. Any and all capacitors downstream of the CTs must be removed
or APF PCS performance will be diminished greatly and/or resonance may
occur.
3. Nonlinear loads with input EMI filters may interact with APF PCS to
prevent proper operation of APF PCS. Removal of these filters is best.
However, if removal is not possible, insertion of a series line reactor
in front of the EMI filter is required.
4. Use of series line reactors in front of all SCR type converters is
best for optimum reduction in harmonics. In some cases line reactors may
be required due to the design of the SCR converter. Consult PQc if questions
arise.
5. PWM VFDs require either a DC bus choke or an input line reactor for
optimum operation with APF PCS.
6. If APF PCS is on an electrical system that contains a combination of
linear and nonlinear loads, all linear loads may be grouped as if they
were one load for the purposes of this selection program.
7. When TDD (total demand distortion of the current) is maintained below
5%, the upstream total harmonic voltage distortion [THD(V)] will not exceed
5% THD(V).
8. APF PCS selection is based solely upon current requirements. Be sure
to select the correct model that matches your system voltage.
9. Be sure to use harmonic distortion percentages based upon the fundamental
current not total 'RMS' current.